This simulation shows how a counter-flow, evaporative cooling tower cools hot water by bringing it into direct contact with air. Water trickles downward through a bed of fill while air is drawn upward; a small fraction of the water evaporates, and that evaporation removes most of the heat from the rest of the water. The simulation solves the Merkel equation for the tower's performance.
Use the sliders to set the hot water inlet temperature, the air's dry-bulb and wet-bulb temperatures, the water-to-air mass ratio (L/G), the packing capability (KaV/L), the inlet water flow rate, and the cycles of concentration. The preset buttons load typical operating conditions.
The schematic shows water cooling as it falls through the fill and air warming and picking up moisture as it rises. The cold water leaving the basin is pumped through a heat exchanger, where it absorbs heat from whatever is being cooled, and returns to the top of the tower as the hot water shown entering the fill — the same water is recirculated continuously around this loop. To minimize build up of dissolved solids in the water in the basin, some water is removed in a blowdown stream. Because of blowdown and because some water evaporates, makeup water is added to the basin to maintain a constant flow rate of water through the system. The enthalpy diagram shows the driving force between the air and the saturation curve. The blue line shows the air enthalpy at the bottom and top of the tower but it uses the water temperature at those locations for the x axis. The middle chart shows water and air temperature through the height of the fill. The third chart shows how the cold water temperature depends on L/G at the current packing capability.
Things to try
The tower is modeled with the Merkel equation, which assumes a Lewis factor of 1 and equal heat- and mass-transfer area:
$$\frac{K_aV}{L}=\int_{T_{cold}}^{T_{hot}} \frac{c_L\,dT}{h^*-h}$$
The operating line comes from an energy balance on the air:
$$h = h_{in} + \frac{L}{G}\,c_L\,(T - T_{cold})$$
where $h^*$ is the enthalpy of saturated air at the local water temperature $T$. The simulation finds the value of $T_{cold}$ that makes the Merkel integral equal to the packing capability $K_aV/L$.
Air humidity through the fill is found by integrating
$$\frac{dW}{dx} = W^*-W$$
over the dimensionless height $x$ (0 at the bottom, 1 at the top), and the air dry-bulb temperature follows from the local $h$ and $W$.
Evaporation, blowdown, and makeup water are
$$E = G\,(W_{out}-W_{in}) \qquad B=\frac{E}{COC-1} \qquad \text{makeup} = E + B$$
Terms used in the results
Symbols
This simulation was created in the Department of Chemical and Biological Engineering at University of Colorado Boulder for LearnChemE.com by John L. Falconer using Claude AI. It was prepared with financial support from the National Science Foundation (DUE 2336987 and 2336988). Address any questions or comments to LearnChemE@gmail.com.